Swartz Watt Transducer

 

Control Systems
Power Systems
Mining Electrics
Transit Electrics
Components
Sheet Metal Fabrication
Back to SMC Home Page
<< Back to Home
Site Index

Contact SMC
Contact SMC

About SMC

Search SMC Web Site

  

SWARTZ®

WATT TRANSDUCER

pdficon.gif (1019 bytes)  PDF Cutsheet

Watt Transducer

(Click on image for enlarged view)

GENERAL.gif (1468 bytes)

 

The SWARTZ® Watt Transducer is a high performance, solid-state unit specifically developed to meet requirements for supervisory control and data acquistion (SCADA) systems. The transducer is ruggedly constructed for the transit substation environment and operates from DC "housekeeping" battery supplies without use of separate AC inverters.

"Power on" LED
Four quadrant multiplier
Overrange capability
Smooth saturation characteristics at range limits
High bandwidth to 1 khz
Bi-Directional
Internal Power Supply operates on and auto-compensates for a wide range of DC inputs
Magnetic link design; no aging deficiencies or temperature drift
Three-way isolation: power supply, input circuit, and output circuit
DESCRIP.gif (1631 bytes)

The Watt Transducer is constructed on a flanged base and may be mounted in any orientation. Electrical connection is via screw terminal barrier strips. "Gain" and "Zero" adjustment trimpots are located on the top cover for calibration or for setting intentional offsets. Voltage and current are multiplied in the high voltage section for highest accuracy and the watts output is fed to a full wave FET chopper that provides high voltage isolation between feeder circuits and current loop output. The output is a bi-polar current source and tracks the input signal with current feedback located in the positive output for best performance.

 

SPEC.gif (1654 bytes)

Input Power: Operates on 24-125VDC
Supply Current:40 mA at 125 VDC, 200 mA at 24 VDC
Ambient Temperature:-20°C to +55°C
Design Test:SWC ANSI/IEEE C37.90
Input Dielectric:3700 VDC, 60 Hz, 1min.
Input Impedance: 2 M ohms
Output:-2 to +2 mA
Output load impedance:Up to 10K ohms
Accuracy at 25°C: + .5% fs
Temperature effect:+ .15% per °C
Scale Factors:0-1000 VDC = 0-1 mA, 0-50 mV = 0-1 mA

Interface Diagram

Relay Case Dimensions

Interface Diagram
Click to Enlarge

Relay Case Dimensions
Click to Enlarge

Components Operation Logo
Fax, shipping, and e-mail address information

For SMC Components Operation

ISO 9001 Logo
A Certified Facility

 

Home ] Up ] About SMC ] Site Index ] Search SMC ]

colorsmc.gif (4151 bytes)

SMC Electrical Products, Inc.    

P.O. Box 880

Barboursville, West Virginia 25504

(304) 736-8933

Go to "Contact SMC" for a company-wide list of fax numbers, shipping addresses, and e-mail addresses

©Copyright SMC Electrical Products, Inc. 1998 & 1999, all rights reserved
Last modified on 09/21/00
Webmaster:  smcelec@smcelectrical.com